Fig. 30: Remove punching outs

Fig. 31: Remove insulation

Fig. 32: Break through openings

Fig. 33: Mounting connecting piece

Adjacent room connection

The indoor unit allows you to cool an adjacent

room via a duct system, e.g. in a suspended

ceiling. The following conditions must be met:

n

Pay attention to local regulations for air treat-

ment.

n

For the adjacent room connection, a flanged

collar with a minimum diameter of NW 150

must be mounting.

n

The cooling capacity of the indoor unit must be

adequate for cooling both rooms.

n

There must be an opening created between

the two rooms that allows the air to circulate

between them.

n

A maximum pipe length of 7 m may not be

exceeded (Fig. 34).

n

To ensure that air is transported to the adja-

cent room, 1 or 2 of the 4 air outlets are to be

sealed on the indoor unit. To do this, use a

black strip with adhesive on one side which is

stuck to the opening(s) to be sealed. The strip

must be able to permanently withstand the

strain from the air pressure.

max. 7 m

A

B

Fig. 34: Adjacent room connection

A: Main room

B: Adjacent room

Fresh air connection

As already described, it is possible to suction in

fresh air (outside air) in addition to the room air

with the indoor unit and regulate the temperature.

This is the preferred alternative in rooms where air

is used up quickly.

n

Pay attention to local regulations for air treat-

ment.

n

For the fresh air connection, a flanged collar

with a minimum diameter of 65 mm must be

mounting (Fig. 35).