Remko mxd – REMKO MXD 202 User Manual

Page 26

background image

A

B

1

Fig. 35: Fresh air connection

1: Fresh air inlet

A: Outdoor

B: Indoor

n

The quantity of fresh air may not exceed 10%

of the nominal circulating air volume; otherwise

it is possible that the unit will not work properly.

n

To prevent rainwater from entering the unit, the

air may only be suctioned in by the fresh air

intake at a maximum speed of 2.5 m/s.

n

To connect the fan, it is necessary for the cus-

tomer to install a separately fused electrical

installation.

In addition, in the following picture framed poly-

styrene partition the drip pan must be removed

with a knife. (Fig. 36).

1

Fig. 36: Fresh air inlet

1: Fresh air inlet

REMKO MXD

26