9

Commissioning

NOTICE!

Commissioning should only be performed by

specially trained personnel and documented

after the certificate has been issued. Observe

the operating manuals for the indoor unit and

outdoor unit when commissioning the entire

system.

Functional test for cooling mode

Check the DIP switch settings on the PCB, as

illustrated on chapter "Choice of unit". If neces-

sary, set the DIP switches to the appropriate

indoor unit type.

1.

Switch the supply voltage on.

2.

Use the remote control to turn on the unit and

select the cooling mode, maximum fan speed

and lowest nominal temperature.

3.

Measure and record all the required values in

the commissioning report and check the

safety functions.

4.

Check the control system for the unit using

the functions described in the chapter "Oper-

ation". Timer, temperature setting, fan

speeds and changing to air circulation or

dehumidifying mode.

5.

Check the correct function of the condensa-

tion line by pouring distilled water into the

condensation tray. A bottle with a spout is

recommended for pouring the water into the

condensation tray.

Functional test for heating mode

1.

Switch the supply voltage on.

2.

Use the remote control to switch on the unit

and select the heating mode, maximum fan

speed and highest nominal temperature.

3.

Measure and record all the required values in

the commissioning report and check the

safety functions.

4.

Measure the air intake temperature of the

ceiling mounted cassette and the room tem-

perature approx. 1.5 m above the floor. In the

event of deviation, correct any temperature

difference by means of the DIP switch SW1

(s.

Ä on page 31).

5.

Check the control system for the unit using

the functions described in the chapter "Oper-

ation". Timer, temperature setting, fan

speeds.

Final tasks

n

Reassemble all disassembled parts.

n

Familiarise the operator with the system.

NOTICE!

Check that the shut-off valves and valve caps

are tight after carrying out any work on the

cooling cycle. Use appropriate sealant prod-

ucts as necessary.

REMKO MXD

34