Installation & wiring, Relay expansion module overview and wiring, Sa e-bus controller technical guide 30 – Orion System SA E-BUS Controller User Manual
Page 30: Relay expansion module, Zone, All comm loop wiring is straight thru, T to t, r to r & shld to shld, 24vac gnd, Sa e-bus controller

Zone
Zone
Installation & Wiring
SA E-BUS Controller Technical Guide
30
12-Relay Expansion Module Overview and Wiring
Figure 25: OE358-23-12R – 12-Relay Expansion Module Wiring and Jumper Settings
12-Relay Expansion Module
Two different Expansion Modules are available for use with the SA E-
BUS Controller to provide additional inputs and outputs beyond those
found on the SA E-BUS Controller.
The SA Expansion Module ( OE333-23-SA) is provided with 8 Binary
Inputs, 4 Analog Inputs, 4 Relay Outputs, and 5 Analog Outputs. See
Figures 16 and 17 on page 20 and 21 for complete wiring details.
The 12-Relay Expansion Module ( OE358-23-12R) provides for 12 Dry
Contact Confi gurable Relay Outputs. See Figure 25 below for complete
wiring details.
EXP1
EXP1
EXP2
EXP2
Line Voltage
All Comm Loop Wiring Is
Straight Thru
24VAC
GND
Local Loop
RS-485
9600 Baud
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
G - Fan ON/OFF Only
R - 24VAC
Relay Output Contacts
R2 Through R5 May Be User-
Configured For The Following:
Note:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command
(VAV Boxes)
4 - Reversing Valve (Air To Air Heat
Pumps)
5 - Reheat Control (Dehumidification)
6 - Preheater For Low Ambient Protection
7 - Alarm
8 - Override
9 - Occupied
10 - Water Side Economizer
A Total Of 20 Relays Are Available
By Adding Expansion Modules. Expansion
Module Relay Outputs Are User-
Configurable As Listed Above.
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere
OE271
Static Pressure
Transducer
Splice If Required
Connect To
12 Relay Expansion Module
Connect To Digital Room Sensor - See Digital Room Sensor
Wiring Diagram.
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
T to T, R to R & SHLD to SHLD
Size Transformer For Correct
Total Load.
SA Controller = 8 VA
SA E-BUS Controller
Note:
All Relay Outputs Are Normally Open And
Rated For 24 VAC Power Only.
1 Amp Maximum Load.
AI1 SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
Jumpers
Note:
Only One SA Controller is Required Whether The SA Unit is a Single Cabinet Or Dual
Cabinet Unit. Additional Wiring For Dual Cabinet Units is Shown and Noted As Such On
The Applicable Single Cabinet Unit Diagrams.
IC DIGITAL
SENSOR
2
IC
EXPANSION
2
STATIC
PRESSURE
LED BLINK CODES
LED NAME
STATUS1 STATUS2
NORMAL OPERATION
0
1
SAT FAIL
1
2
EAT FAIL
2
2
SPC FAIL
3
2
MECH COOL FAIL
1
3
MECH HEAT FAIL
2
3
FAN PROOF FAIL
3
3
DIRTY FILTER
4
3
WATER FLOW ALARM
6
3
DRAIN PAN ALARM
7
3
EMERGENCY SHUTDOWN
5
3
LOW SAT
1
4
HIGH SAT
2
4
CONT. TEMP COOL FAIL
3
4
CONT. TEMP HEAT FAIL
4
4
PUSH BUTTON OVR
1
5
ZONE OVR
2
5
OUTPUT FORCE ACTIVE
0
6
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
AI3
AI4
AI5
AI7
A01
A02
= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= EWT (ENTERING WATER TEMPERATURE SENSOR)
= EAT (ENTERING AIR TEMPERATURE SENSOR)
= NOT USED
= SPACE TEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESET SOURCE
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
ANALOG INPUT
JUMPER
SETTINGS
E-BUS
CONNECTOR
WattMaster Label
#LB102060-01-A
Rev.: 1A
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY
COMMON
SA
CONTROLLER
E-BUS
Orion No.:OE332-23E-VCMX-SA
AAON No.:
V07160