Installation & wiring, Sa expansion module output wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual
Page 21: Warning

SA E-BUS Controller Technical Guide
Installation & Wiring
21
SA Expansion Module Output Wiring
Figure 17: OE333-23-SA – SA Expansion Module Output Wiring
Modular Cable
Connect To SAE-BUS
Controller
Modular Cable
Connect To Expansion
Module (When Used)
24 VAC
GND
10 VA Minimum Power
Required For SA
Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-
to-24VAC. Failure to observe polarity will result in damage to one or more of
the boards. Expansion Module must be wired in such a way that the
expansion module and the controller are always powered together. Loss of
power to the expansion module will cause the controller to become
inoperative until power is restored to the expansion module.
Digital
Compressor Controller
1.) The Modulating Cooling Output Voltage Must Be Configured For
1.5 - 5 VDC Operation When You Are Setting Up The SA Controller
Operating Parameters For The Copeland Digital Compressor.
Note:
COM
COM
+
+
Modulating Heating Signal
(0 to 10 or 2-10 VDC Input)
Modulating
Chilled Water Valve
Or Digital Scroll Compressor
(1.5 5, 0 10 r 2 10 VDC Input)
Cooling Stage 1
Stage 1
-
-
o
-
WSE Bypass Valve B
Actuator
(2-10 VDC)
WSE Bypass Valve A
Actuator
(2-10 VDC)
Configurable Relay Output #1
R1
R2
R3
R4
Configurable Relay Output #2
Configurable Relay Output #3
Configurable Relay Output #4
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions
3 Y1
3 Y1
2 +
2 +
1 COM
1 COM
Note:
1.) The Modulating
Cooling Device Used
Must Be Capable Of
Accepting Either A 0-
10 VDC, 2-10 VDC or
1.5-5.0 VDC Input.
The Modulating
Cooling
Output Voltage
Is User Configurable For
These Voltages. The
Modulating Heating
Devices Used Must Be
Capable of Accepting
Either A 0-10 VDC or 2-
10 VDC Input. The
Modulating Heating
Output Voltage Is User-
Configurable For These
Voltages. These Voltage
Outputs Must Also Be
Configured When You
Are Setting Up The SA
Controller(s) Operating
Parameters.
2.) Each Modulating
Heating Or Cooling
Device Used On The SA
Controller Must Have (1)
Relay Output Configured
For Each Device Used,
In Order To Enable The
Modulating Heating
And/Or Cooling Device's
Sequence. This Relay
Output Must Be
Configured When
Setting Up The SA
Controller Operating
Parameters.
Relay Output Contacts R1 Through
R4 May Be User-Configured For The
Following:
Note:
-
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV
Boxes)
4 - Reversing Valve (Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Preheater For Low Ambient
Protection
7 - Alarm
8 - Override
9 - Occupied
10 - Water Side Economizer
A Total Of 20 Relays Are
Available By Adding Expansion
Modules. Expansion Module Relay
Outputs Are User Configurable As
Listed Above.
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
SA Expansion
Module
A 1
O
AO2
AO3
AO4
AO5
GND
GND
COM
+
Modulating Cooling Stage 2
Digital Scroll Compressor Only
(1.5 - 5 VDC Input)
Note:
See WSE Bypass Wiring
Detail For More
Information.
See Digital Scroll
Wiring Detail For
More Information.
Note:
COM
+
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
SA
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= SUCTION PRESSURE A (0-5 VDC)
= SUCTION PRESSURE B (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
AO1 = MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING COOLING STAGE 2 SIGNAL
(DIGITAL COMPRESSOR ONLY 1.5-5 VDC)
= WSE BYPASS 2A SIGNAL
(0-10 VDC)
= WSE BYPASS 2B SIGNAL
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
BI1 = WATER PROOF OF FLOW - A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
= AIR PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
= DRAIN PAN OVERFLOW - A - N.O. INPUT
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
24 VAC
POWER ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
WattMaster Label
#LB102061-A
Rev.: 1C
SA Expansion Module
Orion No.:OE333-23-SA
AAON No.:
R96180
The SA Expansion Module must be connected to 24 VAC as shown in
the wiring diagram below. Please see Table 1 on page 10 for correct VA
requirements to use when sizing the transformer(s) used for powering
the expansion module.
Also please note that when wiring the SA Expansion Module, its contacts
must be wired as wet contacts (connected to 24 VAC).