Digital Room Sensor Wiring
Digital Room Sensor
The OE217-00 Digital Room Sensor is used to sense Space Temperature
and the OE217-01 Digital Room Sensor is used to sense Space Tem-
perature and Space Humidity. The Sensor connects to the SA E-BUS
Controller with the TSDRSC modular cable. It should be mounted at ap-
proximately 5 ft. above the fl oor on the wall in an area that does not have
drafts or is exposed to direct sunlight. See Figure 6 for wiring details.
I2C DIGITAL
SENSOR
I2C
EXPANSION
STATIC
PRESSURE
ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
0-5V
AI5
AI7
WattMaster Label
#LB102033-01
AI1
I1
SET
AI2 SET
AI3 SET
AI4 SET
AI5 SET
AI7 SET
AI2
AI3
AI4
AI5
AI7
SA E-BUS Controller
Digital Room Sensor
Display
Override
OVERRIDE
ALARM
TSDRSC Cable
Note: The
Connects
Directly To The
Controller Using
A
Of The Appropriate
Length.
Digital Room Sensor
SA E-BUS
TSDRSC Cable
The Maximum Length Allowed Is
160 Feet.
EMERGENCY SHUTDOWN
Note: No Additional Wiring is Required For
Dual Cabinet Units.
Figure 6: OE217-00 & OE217-01 – Digital Room Sensor Wiring