Installation & wiring, Sa expansion module binary inputs wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual
Page 23: 23 sa expansion module binary inputs, Sa expansion module, Warning

SA E-BUS Controller Technical Guide
Installation & Wiring
23
SA Expansion Module Binary Inputs
The SA Expansion Module provides 8 Binary Inputs. See Figure 19
below for detailed wiring.
The transformer used for powering the SA Expansion Module must also
be used to power the binary inputs.
Figure 19: OE333-23-SA – SA Expansion Module 8 Binary Inputs Wiring
Warning: Do not apply any voltage greater than 24 VAC to the
binary inputs. Higher voltages will damage the expansion module
and possibly other components on the system.
BI8
BI7
BI6
BI5
BI3
BI4
BI1
BI2
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable Connect To
Expansion Module
(When Used)
24 VAC
GND
SA Expansion
Module
10 VA Minimum Power Required
For SA Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Module must be wired in such a way that the expansion
module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power
is restored to the expansion module.
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied-N.O. Input
Water Proof of Flow A - N.O. Input
Dirty Filter - N.O. Input
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
SA
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= SUCTION PRESSURE A (0-5 VDC)
= SUCTION PRESSURE B (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
AO1 = MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING COOLING STAGE 2 SIGNAL
(DIGITAL COMPRESSOR ONLY 1.5-5 VDC)
= WSE BYPASS 2A SIGNAL
(0-10 VDC)
= WSE BYPASS 2B SIGNAL
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
BI1 = WATER PROOF OF FLOW - A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
= AIR PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
= DRAIN PAN OVERFLOW - A - N.O. INPUT
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
24 VAC
POWER ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
WattMaster Label
#LB102061-A
Rev.: 1C
SA Expansion Module
Orion No.:OE333-23-SA
AAON No.:
R96180
SA Expansion Module Binary Inputs Wiring