Installation & Wiring
SA E-BUS Controller Technical Guide
20
SA Expansion Module Input Wiring
Figure 16: OE333-23-SA – SA Expansion Module Input Wiring
SA Expansion Module
Two different Expansion Modules are available for use with the SA E-
BUS Controller to provide additional inputs and outputs beyond those
found on the SA E-BUS Controller.
The SA Expansion Module ( OE333-23-SA E-BUS Controller) provides
8 Binary Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable
Relay Outputs. See Figures 16 and 17 for complete wiring details.
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied - N.O. Input
VOUT (0-5V)
0-5V
GND
GND
VIN
VAC OR DC
Water Proof of Flow A - N.O. Input
Dirty Filter - N.O. Input
AI2
AI3
AI4
B 7
I
B 6
I
B 5
I
B 3
I
B 4
I
B 1
I
B 2
I
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable
Connect To Next Expansion
Module (When Used)
24 VAC
GND
Entering Air
Humidity Sensor
Indoor Air
Humidity Sensor
10 VA Minimum Power Required
For SA Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Module must be wired in such a way that the expansion
module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.
SA Expansion Module
AI1
GND
GND
BI8
See Humidity Sensor Wiring
Details For Complete Wiring
Information.
See Suction Pressure
Transducer Wiring Details For
Complete Wiring Information.
Additional Suction
Pressure Sensor Required
On Dual Units Only.
RD
RD
WH
WH
BK
BK
Suction Pressure
Transducer #1
Suction Pressure
Transducer #2
Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
SA
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= SUCTION PRESSURE A (0-5 VDC)
= SUCTION PRESSURE B (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
AO1 = MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING COOLING STAGE 2 SIGNAL
(DIGITAL COMPRESSOR ONLY 1.5-5 VDC)
= WSE BYPASS 2A SIGNAL
(0-10 VDC)
= WSE BYPASS 2B SIGNAL
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
BI1 = WATER PROOF OF FLOW - A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
= AIR PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
= DRAIN PAN OVERFLOW - A - N.O. INPUT
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
24 VAC
POWER ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
WattMaster Label
#LB102061-A
Rev.: 1C
SA Expansion Module
Orion No.:OE333-23-SA
AAON No.:
R96180
The 12-Relay Expansion Module ( OE358-23-12R) provides for 12
Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete
wiring details.
The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.