Installation & wiring, Indoor wall-mounted humidity sensor wiring, Sa e-bus controller technical guide – Orion System SA E-BUS Controller User Manual
Page 25: 25 indoor wall-mounted humidity sensor, Figure 21, Space humidity sensor sa expansion module, Ai2 gnd
SA E-BUS Controller Technical Guide
Installation & Wiring
25
Indoor Wall-Mounted Humidity Sensor
When used, the OE265-11 Indoor Wall-Mounted Humidity Sensor is
connected to the system by wiring it to the AI2 input on the SA Expan-
sion Module. It must be wired as shown in Figure 21 below for proper
controller operation.
Warning: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the Space Humidity
Sensor or SA Expansion Module.
Figure 21:
OE265-11 – Indoor Wall-Mounted Humidity Sensor Wiring
Indoor Wall-Mounted Humidity Sensor Wiring
AI2
GND
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable
Connect To Expansion
Module (When Used)
24 VAC
GND
10 VA Minimum Power Required
For SA Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and
24VAC-to-24VAC. Failure to observe polarity will result in damage to
one or more of the boards. Expansion Module must be wired in such a
way that the expansion module and the controller are always powered
together. Loss of power to the expansion module will cause the
controller to become inoperative until power is restored to the
expansion module.
Jumper Must
Be Set To
0-5V As
Shown
Jumpers Must Be
Set as Shown
For Correct
O-5 VDC
Operation
1 & 3 Are Off
2 & 4 Are On
Jumpers Must Be
Set as Shown For
Normal
1, 2, 4, 5 & 6 Are Off
3 Is On
Operation Of
Sensor
Vo
Zero
Span
Gnd
Vi
n
Io
4
4
4
4
5
5
6
6
ON
ON
ON
ON
3
3
3
3
2
2
2
2
1
1
1
1
Space Humidity Sensor
SA Expansion
Module
Note: No Additional
Wiring is Required For
Dual Cabinet Units.
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
AO1 = BUILDING PRESSURE CONTROL VFD OR
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
= MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING/DIGITAL SCROLL
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= RETURN AIR DAMPER ACTUATOR
(0-10 VDC)
= RETURN AIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
BI1 = HOOD ON - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED
www.orioncontrols.com
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
WattMaster Label
#LB102034-01
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
+V
SIG
GND
PR OUT
GND
SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR
TO VCM-X INPUT
TERMINALS AI5 & GND
OE333-23-EM-A VCM-X EXPANSION MODULE
WA
RN
IN
G
OB
SE
RV
E
POLAR
IT
Y
SA
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
AI2
AI3
AI4
GND
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
= SUCTION PRESSURE A (0-5 VDC)
= SUCTION PRESSURE B (0-5 VDC)
= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS
AO1 = MODULATING HEATING SIGNAL
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
= MODULATING COOLING STAGE 2 SIGNAL
(DIGITAL COMPRESSOR ONLY 1.5-5 VDC)
= WSE BYPASS 2A SIGNAL
(0-10 VDC)
= WSE BYPASS 2B SIGNAL
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS
AO2
AO3
AO4
AO5
GND
GND
ANALOG INPUT
JUMPER SETTINGS
MUST BE SET AS
SHOWN FOR
PROPER
OPERATION
AI1
AI2
AI3
AI4
THERM
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
4-20mA
0-10V
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
0-5V
ANALOG INPUT
JUMPER
SETTINGS
RELAY 1 =
RELAY 3 =
RELAY 2 =
RELAY 4 =
IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)
NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
BI1 = WATER PROOF OF FLOW - A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
= AIR PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
= DRAIN PAN OVERFLOW - A - N.O. INPUT
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI3
BI4
BI5
BI6
BI7
BI8
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 4
RELAY
COMMON
I2C
EXPANSION
I2C
EXPANSION
24 VAC
POWER ONLY
WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
WattMaster Label
#LB102061-A
Rev.: 1C
SA Expansion Module
Orion No.:OE333-23-SA
AAON No.:
R96180