beautypg.com

Bacnet ip – Nortec BACnet User Manual

Page 8

background image

BACnet & LONWORKS Supplemental Install Manual | 4

BACnet IP

For BACnet IP networks, the recommended wire type is standard Category 5 Ethernet Cable
(CAT 5) with RJ-45 terminations (Category 5E and category 6 cable are also acceptable). Refer
to the BMS supplier for maximum recommended lengths of CAT5 cable.

Table 2: BACnet IP Parameters

Signal Type

BACnet IP

Recommended Cable

Address

Maximum
Recommended Distance
from NORTEC Humidifier

Transmission

Mode

Port

Node

ID

Device

Instance

LAN
Standard

UDP

47808

Category 5 Ethernet
Cable (CAT 5 or better)
with RJ-45 termination

79*

12*

Depends on cable
manufacturer, refer to
BMS Supplier for
recommendations

*Default, may vary for multi-unit orders.

Wiring connections are made directly to the integrated controller circuit board.

Figure 1:

Location of Integrated Controller Board

shows the location of the board inside the NH-EL.

Figure 1: Location of Integrated Controller Board

This manual is related to the following products: