beautypg.com

Addressing and communication, Bacnet communication set-up – Nortec BACnet User Manual

Page 12

background image

BACnet & LONWORKS Supplemental Install Manual | 8

Addressing and Communication

After wiring connections have been completed, the humidifier needs to be setup to operate and
communicate through the BACnet interface.

BACnet Communication Set-up

The following table demonstrates the default addressing found on the NH-EL:

Table 3: BACnet Specific Defaults

BACnet IP

BACnet MSTP

Default IP addressing

IP Type: DHCP
IP: 192.168.168.243
Subnet: 255.255.255.000
Gateway: 192.168.168.101

N/A

Default BACnet Address
(MAC address)

79

79

Default BACnet Node ID
(Device Instance)

12

1001

Locating the IP addressing in the NH-EL is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > Network Parameters >

Note: By default, the NH-EL will have BACnet disabled. To enable BACnet, select BACnet IP or
BACnet MSTP
under BACnet Parameters. Select the respective protocol and confirm the
selection by pressing the Check Mark button. This action is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters >

Once BACnet is enabled, addressing can be modified as desired.
Locating the BACnet Address (MAC address) in the NH-EL is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters > BACnet MSTP
address

Locating the BACnet Node ID (Device Instance) in the NH-EL is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters > Node ID




This manual is related to the following products: