Addressing and communication, Control signal setting – Nortec BACnet User Manual
Page 21

17 | BACnet & LONWORKS Supplemental Install Manual
Addressing and Communication
After wiring connections have been completed, the humidifier needs to be setup to operate and 
communicate through the interface. The initial step is to configure the Control settings to 
ensure the humidifier points to the installed option. 
Control Signal Setting
By default the humidifier is configured operate on a hardwired control signal supplied through 
the unit terminal strip. This can be changed to allow the humidifier to function entirely through 
its Optional interface. 
To adjust this setting:
1 Press the Menu icon on the lower left corner of the screen, to access the menu. 
2 When prompted for a password, enter 0335 using the number pad. Press the Check Mark 
icon to confirm.
3 Select the Configuration menu. 
4 Select the Control Settings menu. The following settings can be adjusted: 
Table 8: BTL / Lonworks Control Signal Parameters
Source
Analog:  Use hardwired control signal 
Modbus: Write control signal through BTL Certified BACnet Option 
LonWorks: Write control signal through LonWorks Option 
Control Mode
Demand: Use a demand control signal 
RH P: Use a sensor value and proportional 
RH PI: Use a sensor value and proportional-integral control band 
Control Channels
Single: Use a single channel control signal 
Dual: Use a dual channel control signal 
Note: Refer to the CONTROL SETTING section of the NH-EL Installation and Operation Manual 
for more information on the above settings. 
 
5 Press Back repeatedly to return to the home screen when complete. 
This procedure is summarized below: 
Main Menu > 0335 > Configuration > Control Settings > 
 
Source: Analog, Modbus, LonWorks 
Control Mode: Demand, RH P, or RH PI 
Control Channels: Single or Dual 
 
 