Control mapping – Nortec BACnet User Manual
Page 14
BACnet & LONWORKS Supplemental Install Manual | 10
Control Mapping
Table 5: BACnet Object Definition List
Parameter
Name
Description
BACnet
ID
Format
Range
Unit
R/W
Details
Dinput_A1
Write RH or
Demand signal
value to control
channel 1 for
cylinder A
10044 Integer 0 - 100 %
Write
Requires BACnet to be enabled.
For most common configurations,
this is the primary control signal
Dinput_A2
Write RH or
Demand signal
value to control
channel 2 for
cylinder A
10045 Integer 0 - 100 %
Write Requires BACnet to be enabled.
Dinput_B1
Write RH or
Demand signal
value to control
channel 1 for
cylinder B
10046 Integer 0 - 100 %
Write
Requires BACnet to be enabled.
Only applies to NH-EL-150 and
NH-EL-200 with dual channel
control enabled
Dinput_B2
Write RH or
Demand signal
value to control
channel 2 for
cylinder B
10047 Integer 0 - 100 %
Write
Requires BACnet to be enabled.
Only applies to NH-EL-150 and
NH-EL-200 with cylinders dual
channel control enabled and
cylinders in independent
operation mode
Manual_
Capcity_A
Sets a manual
capacity limit
restriction for
cylinder A
10008 Integer 0 - 100 %
Write
Limits output to percentage of
total cylinder capacity (for single
cylinder) or for cylinder A (NH-EL-
150 and NH-EL-200 models only)
Manual_
Capcity_B
Sets a manual
capacity limit
restriction for
cylinder B (if
present)
10027 Integer 0 - 100 %
Write
Limits output to percentage
capacity for cylinder B (NH-EL-
150 and NH-EL-200 models only)
BMS_
Timeout
BMS timeout
for Modbus and
BACnet
10043 Integer 0 - 300 s
Write
It is recommend to not change
the value from the factory default
(300)
Remote_
Disable
Remotely
disable steam
production for
the unit
25
Integer 0 or 1
-
Write
0 = Idle/Humidify
1 = Disabled
SP_Chan_
A1
Writes the
desired space
setpoint for
control channel
1 for cylinder A
10010 Integer 0 - 95
%
Write
Use only when Control Mode (14)
is set to RHp or RHpi
Use only when sending RH values
to Dinput_A1.
For most common configurations
this is the primary space
setpoint.