Nortec BACnet User Manual
Page 15
11 | BACnet & LONWORKS Supplemental Install Manual
SP_Chan_
A2
Writes the
desired space
setpoint for
control channel
2 for cylinder A
10013 Integer 10 - 95 %
Write
Use only when sending RH value
to Dinput_A2 with dual channel
control enabled
SP_Chan_
B1
Writes the
desired space
setpoint for
control channel
1 for cylinder B
10016 Integer 0 - 95
%
Write
Use only with NH-EL-150 and NH-
EL-200 models when sending RH
value to Dinput_B1 and cylinders
are in independent operation
mode
SP_Chan_
B2
Writes the
desired space
setpoint for
control channel
2 for cylinder B
10019 Integer 10 - 95 %
Write
Use only with NH-EL-150 and NH-
EL-200 models when sending RH
value to Dinput_B2 with dual
channel control enabled and
cylinders are in independent
operation mode
Signal_
Source
Selects signal
source to
control unit
13
Integer 0 - 4
-
Write
0 = Analog
1 = Modbus
2 = BACnet/IP
3 = BACnet/MS
4 = LonWorks
Control_M
ode
Selects method
to control unit
14
Integer 1 - 3
-
Write
1 = Demand
2 = RH P
3 = RH PI
Control_
Channel
Selects method
to control
channels
15
Integer 0 - 1
-
Write
0 = Single Channel
1 = Dual Channel
Input_A1
Displays
channel 1
demand for
cylinder A
10001 Integer 0 - 100 %
Read
Displays channel 1
demand/sensed RH as a
percentage of cylinder capacity
for cylinder A
Input_A2
Displays
channel 2
demand for
cylinder A
10002 Integer 0 - 100 %
Read
Displays channel 2
demand/sensed RH as a
percentage of cylinder capacity
for cylinder A
Input_B1
Displays
channel 1
demand for
cylinder B
10003 Integer 0 - 100 %
Read
Displays channel 1
demand/sensed RH as a
percentage of cylinder capacity
for cylinder B (NH-EL-150 and
NH-EL-200 models only)
Input_B2
Displays
channel 2
demand for
cylinder B
10004 Integer 0 - 100 %
Read
Displays channel 2
demand/sensed RH as a
percentage of cylinder capacity
for cylinder B (NH-EL-150 and
NH-EL-200 models only)
Blower_
Pack_A
Reads the
status of the
blower pack for
cylinder A
4
Integer 0 or 1
-
Read
0 = Open
1 = Closed