Control signal setting – Nortec BACnet User Manual
Page 13

9 | BACnet & LONWORKS Supplemental Install Manual
Control Signal Setting
By default the humidifier is configured to operate on a hardwired control signal supplied through 
the unit terminal strip. This can be changed to allow the humidifier to function entirely through 
its BACnet interface. 
*Note: the Humidifier Security loop will still need to be enabled for humidifier to run. 
To adjust this setting:
1 Press the Menu icon on the lower left corner of the status screen, to access the menu. 
2 When prompted for a password, enter 0335 using the number pad. Press the Check Mark 
icon to confirm.
3 Select the Configuration menu. 
4 Select the Control Settings menu. The following settings can be adjusted: 
Table 4: Control Signal Parameters
Source
Analog:  Use hardwired control signal 
BACnet/IP: Write control signal through BACnet/IP interface 
BACnet/MS: Write control signal through BACnet/MS interface 
Control Mode
Demand: Use a demand control signal 
RH P: Use a sensor value and proportional 
RH PI: Use a sensor value and proportional-integral control band 
Control Channels
Single: Use a single channel control signal 
Dual: Use a dual channel control signal 
Note: Refer to the CONTROL SETTING section of the NH-EL Installation and Operation Manual 
for more information on the above settings. 
 
5 Press Back repeatedly to return to the home screen when complete. 
This procedure is summarized below: 
Main Menu > 0335 > Configuration > Control Settings > 
 
Source: Analog, BACnet/IP, BACnet/MS, 
Control Mode: Demand, RH P, or RH PI 
Control Channels: Single or Dual 
