Appendix b – Nortec BACnet User Manual
Page 30

BACnet & LONWORKS Supplemental Install Manual | 26
APPENDIX B
Table 13: Parameters
Parameter Name
Description
SNVT
#
SNVT
Range
NV
Index
R/W Details
nviDRHDem_A1
Write RH or 
Demand signal 
value to control 
channel 1 for 
cylinder A 
81
Lev_percent 0 - 100
23
W
Requires LonWorks 
to be enabled. 
For most common 
configurations, this 
is the primary 
control signal 
nviDRHDem_A2
Write RH or 
Demand signal 
value to control 
channel 2 for 
cylinder A 
81
Lev_percent 0 - 100
24
W
Requires LonWorks 
to be enabled. 
 
nviDRHDem_B1
Write RH or 
Demand signal 
value to control 
channel 1 for 
cylinder B 
81
Lev_percent 0 - 100
33
W
Requires LonWorks 
to be enabled. 
Only applies to NH-
EL-150 and NH-EL-
200 with dual 
channel control 
enabled 
nviDRHDem_B2
Write RH or 
Demand signal 
value to control 
channel 2 for 
cylinder B 
81
Lev_percent 0 - 100
34
W
Requires LonWorks 
to be enabled. 
Only applies to NH-
EL-150 and NH-EL-
200 with cylinders 
dual channel 
control enabled and 
cylinders in 
independent 
operation mode 
nviManCapacity_A
Sets a manual 
capacity limit 
restriction for 
cylinder A 
81
Lev_percent 0 - 100
15
W
Limits output to 
percentage of total 
cylinder capacity 
(for single cylinder) 
or for cylinder A 
(NH-EL-150 and 
NH-EL-200 models 
only) 
nviManCapacity_B
Sets a manual 
capacity limit 
restriction for 
cylinder B (if 
present) 
81
Lev_percent 0 - 100
30
W
Limits output to 
percentage capacity 
for cylinder B (NH-
EL-150 and NH-EL-
200 models only) 
nviBMStimeout
BMS timeout 
for Modbus and 
BACnet 
107
SNVT_time_
sec 
0 - 300
5
W
It is recommend to 
not change the 
value from the 
factory default 
(300) 
nviDisable
Remotely disable 
steam production 
for the unit 
95
Switch
0 or 1
44
W
0 = Idle/Humidify 
1 = Disabled 
