Appendix b – Nortec BACnet User Manual

Page 30

background image

BACnet & LONWORKS Supplemental Install Manual | 26

APPENDIX B

Table 13: Parameters

Parameter Name

Description

SNVT

#

SNVT

Range

NV

Index

R/W Details

nviDRHDem_A1

Write RH or
Demand signal
value to control
channel 1 for
cylinder A

81

Lev_percent 0 - 100

23

W

Requires LonWorks
to be enabled.
For most common
configurations, this
is the primary
control signal

nviDRHDem_A2

Write RH or
Demand signal
value to control
channel 2 for
cylinder A

81

Lev_percent 0 - 100

24

W

Requires LonWorks
to be enabled.

nviDRHDem_B1

Write RH or
Demand signal
value to control
channel 1 for
cylinder B

81

Lev_percent 0 - 100

33

W

Requires LonWorks
to be enabled.
Only applies to NH-
EL-150 and NH-EL-
200 with dual
channel control
enabled

nviDRHDem_B2

Write RH or
Demand signal
value to control
channel 2 for
cylinder B

81

Lev_percent 0 - 100

34

W

Requires LonWorks
to be enabled.
Only applies to NH-
EL-150 and NH-EL-
200 with cylinders
dual channel
control enabled and
cylinders in
independent
operation mode

nviManCapacity_A

Sets a manual
capacity limit
restriction for
cylinder A

81

Lev_percent 0 - 100

15

W

Limits output to
percentage of total
cylinder capacity
(for single cylinder)
or for cylinder A
(NH-EL-150 and
NH-EL-200 models
only)

nviManCapacity_B

Sets a manual
capacity limit
restriction for
cylinder B (if
present)

81

Lev_percent 0 - 100

30

W

Limits output to
percentage capacity
for cylinder B (NH-
EL-150 and NH-EL-
200 models only)

nviBMStimeout

BMS timeout
for Modbus and
BACnet

107

SNVT_time_
sec

0 - 300

5

W

It is recommend to
not change the
value from the
factory default
(300)

nviDisable

Remotely disable
steam production
for the unit

95

Switch

0 or 1

44

W

0 = Idle/Humidify
1 = Disabled