29 | BACnet & LONWORKS Supplemental Install Manual

nvoSysDem_B

Reads the demand
for cylinder B

81

Lev_percent

0 –

100

29

R

Demand Mode:
Summation of
Input_B1 and
Input_B2
RH Mode:
PID calculation

nvoSecurity_A

Reads the status
of the safety loop
for cylinder A

95

Switch

0 or 1

45

R

0 = Open
1 = Closed

nvoSecurity_B

Reads the status
of the safety loop
for cylinder B

95

Switch

0 or 1

48

R

0 = Open
1 = Closed

nvoHourOpt_A

Reads operating
time for cylinder A

124

SNVT_time_
hour

0 -

5000

10

R

Displays the total
time (hrs) cylinder A
has been running
since last reset

nvoHourOpt_B

Reads operating
time for cylinder B

124

SNVT_time_
hour

0 -

5000

25

R

Displays the total
time (hrs) cylinder B
has been running
since last reset

nvoHourWeight_A

Reads the
weighted time for
cylinder A

124

SNVT_time_
hour

0 -

5000

11

R

An equated run
time (hrs) based on
Run_Time_A x
System_Demand_A

nvoHourWeight_B

Reads the
weighted time for
cylinder B

124

SNVT_time_
hour

0 -

5000

26

R

An equated run
time (hrs) based on
Run_Time_B x
System_Demand_B