Nortec BACnet User Manual
Page 17
13 | BACnet & LONWORKS Supplemental Install Manual
System_
Demand_A
Reads the
demand for
cylinder A
10057 Integer
0 –
100
%
Read
Demand Mode:
Summation of Input_A1 and
Input_A2
RH Mode:
PID calculation
System_
Demand_
B
Reads the
demand for
cylinder B
10058 Integer
0 –
100
%
Read
Demand Mode:
Summation of Input_B1 and
Input_B2
RH Mode:
PID calculation
Safety_
Loop_A
Reads the
status of the
safety loop for
cylinder A
3
Integer 0 or 1
-
Read
0 = Open
1 = Closed
Safety_
Loop_B
Reads the
status of the
safety loop for
cylinder B
5
Integer 0 or 1
-
Read
0 = Open
1 = Closed
Run_Time
_A
Reads
operating time
for cylinder A
10060 Integer
0 -
5000
Hrs
Read
Displays the total time cylinder A
has been running since last reset
Run_Time
_B
Reads
operating time
for cylinder B
10079 Integer
0 -
5000
Hrs
Read
Displays the total time cylinder B
has been running since last reset
Weighted_
Hours_A
Reads the
weighted time
for cylinder A
10061 Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_A x
System_Demand_A
Weighted_
Hours_B
Reads the
weighted time
for cylinder B
10080 Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_B x
System_Demand_B