Nortec BACnet User Manual
Page 31
27 | BACnet & LONWORKS Supplemental Install Manual
nviSetPoint_A1
Writes the desired
space setpoint for
control channel 1
for cylinder A
81
Lev_percent
0 - 95
21
W
Use only when
sending RH values
to Dinput_A1.
Use only when
nviCtrlMode (3) is
set to RHp or RHpi
For most common
configurations this
is the primary space
setpoint
nviSetPoint_A2
Writes the desired
space setpoint for
control channel 2
for cylinder A
81
Lev_percent 10 - 95
22
W
Use only when
sending RH value to
Dinput_A2 with dual
channel control
enabled
nviSetPoint_B1
Writes the desired
space setpoint for
control channel 1
for cylinder B
81
Lev_percent
0 - 95
36
W
Use only with NH-
EL-150 and NH-EL-
200 models when
sending RH value to
Dinput_B1 and
cylinders are in
independent
operation mode
nviSetPoint_B2
Writes the desired
space setpoint for
control channel 2
for cylinder B
81
Lev_percent 10 - 95
37
W
Use only with NH-
EL-150 and NH-EL-
200 models when
sending RH value to
Dinput_B2 with
dual channel
control enabled and
cylinders are in
independent
operation mode
nviSigSource
Selects signal
source to control
unit
81
Lev_percent
0 - 4
2
W
0 = Analog
1 = Modbus
2 = BACnet/IP
3 = BACnet/MS
4 = LonWorks
nviCtrlMode
Selects method to
control unit
81
Lev_percent
1 - 3
3
W
1 = Demand
2 = RH P
3 = RH PI
nviCtrlChannel
Selects method to
control channels
81
Lev_percent
0 - 1
4
W
0 = Single Channel
1 = Dual Channel
nvoRHDem_A1
Displays channel 1
demand for
cylinder A
81
Lev_percent 0 - 100
12
R
Displays channel 1
demand/sensed RH
as a percentage of
cylinder capacity for
cylinder A
nvoRHDem_A2
Displays channel 2
demand for
cylinder A
81
Lev_percent 0 - 100
13
R
Displays channel 2
demand/sensed RH
as a percentage of
cylinder capacity for
cylinder A
nvoRHDem_B1
Displays channel 1
demand for
cylinder B
81
Lev_percent 0 - 100
27
R
Displays channel 1
demand/sensed RH
as a percentage of
cylinder capacity for
cylinder B (NH-EL-
150 and NH-EL-200
models only)