Nortec BACnet User Manual
Page 16
BACnet & LONWORKS Supplemental Install Manual | 12
Blower_
Pack_B
Reads the
status of the
blower pack for
cylinder B
6
Integer 0 or 1
-
Read
0 = Open
1 = Closed
Fan_
Activate_A
Indicates if air
handle or
furnace is
activated for
cylinder A
1
Integer 0 or 1
-
Read
0 = Not Activated
1 = Activated
Fan_
Activate_B
Indicates if air
handle or
furnace is
activated for
cylinder B
2
Integer 0 or 1
-
Read
0 = Not Activated
1 = Activated
Do_Fault_
A
Reads the
status of a fault
on the unit
69
Integer 0 or 1
-
Read
0 = No Fault
1 = Fault
Do_
Service_A
Reads the
status of a
service request
on the unit
67
Integer 0 or 1
-
Read
0 = No Service Required
1 = Service Required
Humidifier
_
Status_A
Reads the
status of the
unit for cylinder
A
36
Integer 0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack
Humidifier
_
Status_B
Reads the
status of the
unit for cylinder
A
57
Integer 0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack