beautypg.com

Nortec BACnet User Manual

Page 16

background image

BACnet & LONWORKS Supplemental Install Manual | 12

Blower_
Pack_B

Reads the
status of the
blower pack for
cylinder B

6

Integer 0 or 1

-

Read

0 = Open
1 = Closed

Fan_
Activate_A

Indicates if air
handle or
furnace is
activated for
cylinder A

1

Integer 0 or 1

-

Read

0 = Not Activated
1 = Activated

Fan_
Activate_B

Indicates if air
handle or
furnace is
activated for
cylinder B

2

Integer 0 or 1

-

Read

0 = Not Activated
1 = Activated

Do_Fault_
A

Reads the
status of a fault
on the unit

69

Integer 0 or 1

-

Read

0 = No Fault
1 = Fault

Do_
Service_A

Reads the
status of a
service request
on the unit

67

Integer 0 or 1

-

Read

0 = No Service Required
1 = Service Required

Humidifier
_
Status_A

Reads the
status of the
unit for cylinder
A

36

Integer 0 - 9

-

Read

0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack

Humidifier
_
Status_B

Reads the
status of the
unit for cylinder
A

57

Integer 0 - 9

-

Read

0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack

This manual is related to the following products: