Installation
Section 3-3-3: Heat Shields
Installing a Wall Mounted RHS7/RHS8 Heat shield
The RHS7/RHS8 Heat shield CANNOT be used when the Termination is
WITHIN 36" horizontal or 60" vertically from the fireplace, or directly off
the rear of the fireplace, as shown figure 20a. The RHS100/RHS101 Heat
Shield (Figure 21 and 21a) MUST be used within the noted dimensions.
To install the RHS7/RHS8, frame an opening in combustible construction,
Figure 20 below. Slide the Heat shield in place over the vent pipe which
attaches to the fireplace. After the fireplace and vent pipe has been
installed, clearances should match the dimensions in Figure 20.
Note: RHS7 is for H*34DL* models only. RHS8 is for H38DL* and
H42DL* models only.
Figure 20. RHS7 / RHS8 Installation. (Install by sliding over vent pipe where it
passes through the combustible construction).
Figure 21. RHS100 / RHS101 Installation. (Install by sliding Outer Section over
vent pipe where it passes through the combustible construction.
Figure 21a. Heat Shield. After sliding the outer section in place.
Installing a Wall Mounted RHS100/RHS101 Heat shield.
The RHS100/RHS101 Heat shield MUST be used where the RHS7/RHS8
Termination (Figure 20 and 20a) CANNOT be used. Use the RHS100/
RHS101 where any of the dimensions are within the parameters
shown, figure 20a.
To install the RHS100/RHS101, Slide the Inner Section over the vent
pipe that will connect to the fireplace. Fasten the vent pipe to the back
of the fireplace with a Min. of three sheet metal screws.
Next, slide the RHS100/RHS101 outer section from the outside of the
structure, see Figure 21.
To complete the installation fasten the Heat Shield Outer Section &
Termination frame to the structure Figure 21a.
Note: RHS100 is for H*34DL* models only. RHS101 is for H38DL* and
H42DL* models only
Figure 20a. RHS7 / RHS8 Installation. (Minimum requirements).
Figure 21b.
RHS100 / RHS101 Installation.
RHS8 Heat Shield
RHS7 or
1” Min. Both sides Typical
1” Min.
1” Min.
Combustible Framing
Combustible
framing
Termination
Drywall / sheetrock
RHS100 or RHS101 Heat Shield
Outer Section
Vent pipe, from fireplace
RHS100 or RHS 101 Heat Shield
Inner Section
Termination
Drywall / sheetrock
Outer Section
RHS100 or RHS101 Heat Shield
RHS100 or RHS 101 Heat Shield
Inner Section
RHS8 Heat
Shield
36” Min
RHS7 or
60” Min
Outer Shield
3/8” Min. Both sides Typical
3/8” Min.
3/8” Min .
Combustible Framing
Inner Shield