CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION

(continued)

Network Hubs

The Network Hub module makes up the
backbone or Main Bus of the network. Multiple
Network Hubs can be configured to increase the
size of the network or to increase the number of
available ports in an installation location. Up to 50
Network Hubs can be connected on a single
network with a patch cable length of up to 2000
feet. Refer to the ConviaNet Design Guide for
more information.

Mounting Holes

120V SYSTEM

Part

Walkerflex

Number

Phase

Configurations

NVHUBA

A

111, 211, 311

NVHUBB

B

211, 311

NVHUBC

C

311

NVHUBD

222

NVHUBF

Field Wired

277V SYSTEM

Part

Walkerflex

Number

Phase

Configurations

LVHUBA

A

111, 211, 311

LVHUBB

B

211, 311

LVHUBC

C

311

LVHUBF

Field Wired

LVHUBF

Field Wired

Table A – NETWORK HUB POWER CONFIGURATIONS

Step 1:

Mount Network Hub securely using
appropriate screws and anchors.

RJ11 Jack for Main

Bus Connections

RJ45 Jacks for Node

Bus Connections

RJ11 Jack for Main

Bus Connections

Step 2:

Connect Power to Network Hub.

For Modular Connection: Connect Convia

Enable Walkerflex Modular Cable
to modular input.

For Field Wired Units: Connect conduit to appropriate

conduit opening and wire per the National Electric
Code. (See Wiring Schematic below or on product
label for connections.

Hub Wiring Schematic

Prewired 5-Port Network Hub

Field Wired 5-Port Network Hub

Power input coming
from Distribution Box
or main panel

Current Flow
Direction

3/4" Trade Size
Knockout

1/2" Trade Size
Knockout

Step 3:

Connect Wiremold Convia Enabled pre-terminated
RJ11 cables between the Network Hubs. Install
Communication Loop Closures into RJ11 ports at the
beginning and end of the network run (Main Bus).

Step 4:

Install Wiremold Convia Enabled pre-terminated
RJ45 cables between the Network Hubs and the
Relay Dimmers, Power Modules, Sims, Switches,
and Scene Controllers.

Wiremold Convia
Enabled Pre-terminated
RJ11 Cable to next
Network Hub in network

Communications Loop
Closure – 2 required
for each network

NOTE: To ensure proper network functioning, Communication

Loop Closures need to be installed into the beginning
and end of the Main Bus of the network. If there is
only one Network Hub in the installation, then
Communication Loop Closures must be installed in
both RJ11 ports on the Network Hub.

Wiremold Convia Enabled Pre-
terminated RJ45 Cables going
to Relay Dimmers, Power
Modules, Sims, Switches and
Scene Controllers

Step 5:

Move on to the installation of Relay Dimmers
and Power Modules.