beautypg.com

Legrand Convia Enabled Walkerflex System User Manual

Walkerflex, System, Convia

background image

Convia

®

Enabled

Walkerflex

®

System

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 1 008 478 – August 2009

Wiremold electrical systems conform to and should be properly
grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold electrical products
may bear the mark as UL Listed and/or Classified and
should be installed in conformance with current local and/or the
National Electrical Code.

IMPORTANT: Please read all instructions

before beginning.

Products Covered:

NVHUB, LVHUB, NRD1, NRD2, LRD1, LRD2, NPM12, NPM22, NPM24, NPM44, NPM24PF,
NPM44PF, CNDU, CLDU, CNWC, CLWC, CNPA, CLPA, CNCS, CLCS, CNCBS, CLCBS, CNCW,
CLCW, CAP3456 & CAP810

NOTE:

Label on product indicates which products are suitable for use in air handing spaces
in accordance with Sec. 300-22(C) of the National Electric Code.

1. Each Convia

®

Enabled Walkerflex

®

System connector

contains a color coded key that indicates rating, conductor
location and orientation. Only like colored keys can be
mated. See Key Configuration and Color Chart on page 11
for available options. Each key is comprised of one or more
configurations.

2. Disconnect power from source prior to wiring any Walkerflex

component into the building’s electrical power system.

3. Installer to determine the maximum power cable length

based on wire gauge and circuit load.

4. Installer to ensure adequate overload protection based on

the system key, rating and circuit load.

5. Refer to appropriate Wiring Diagram and System Key

Configuration Conductor Location Chart for field connections
of Cat. Nos. CNWC/CLWC (Wire Connector) and
CNCW/CLCW (Cable Whips). Refer to wiring diagram
supplied with CNDU/CLDU (Distribution Unit) for field
termination.

6. Securing and Supporting of Cables and Components: Refer

to NEC Article 604, Manufacturing Wiring Systems and any
local codes.

7. Cap all unused connector openings with Cat. No. CAP3456

(for 3 through 6 wire system) or Cat. No. CAP810 (for 8 and
10 wire system).

8. All Convia Enabled accessories are available in a 3-6 wire

and 8-10 wire system and are rated 20A, 120V.

9. 277V Convia Enabled Walkerflex components are only

available in 3-6 wire configurations.

10. The Convia Enabled Walkerflex system is compatible with

the standard Walkerflex system of the same configuration
and key.

GENERAL INFORMATION