Legrand WKD ProSeries Underfloor Duct Rectangular Floor Box Covers User Manual
Page 2
OMNIBOX TRIM FLANGE INSTALLATION:
1. Install adjusting screws in box by sliding the beveled head
under the retaining slot.
2. Secure the trim flange by inserting a narrow blade
screwdriver through the adjusting screw holes and turning
counterclockwise (Make small adjustments to avoid
binding the screws).
3. If installing on a tile or wood floor, apply a bead of silicone
around the underside of the flange to prevent water from
leaking into the outlet box.
PLASTIC OR ALUMINUM
DUPLEX RECEPTACLE COVER:
1. Connect wires to receptacle and attach to
trim flange.
2. Place gasket support plate over receptacle
and attach with #6 truss head screw.
3. Place gasket over the support plate.
4. Attach cover with four (4) flat head screws.
PLASTIC & ALUMINUM
GFCI RECEPTACLE COVER:
1. Connect wires to receptacle and attach to
trim flange.
2. Place gasket support plate over receptacle.
3. Place gasket over the support plate.
4. Attach cover with four (4) flat head screws.
Retaining
Slot
CAT. NO. 827PCC SHOWN
CAT. NO. 828PR SHOWN
CAT. NO. 828PRGFI SHOWN
CAT. NO. 828DPGFITCAL
SHOWN
CAT. NO. 828DPGFITC
SHOWN
Support
Plate
NOTE: Plastic covers may be used with
aluminum trim flanges. Attach plastic
covers using #8-32 machine screws.
Gasket
BRASS DUPLEX RECEPTACLE COVER
(828R & 828DPGFITC:
1. Connect wires to receptacle and attach to
trim flange.
2. Place gasket support plate over receptacle.
Attach with #6 truss head screw.
3. Place gasket over support plate.
4. Attach cover with four (4) flat head screws.
BRASS GFCI RECEPTACLE COVER
(828GFITC:
1. Connect wires to receptacle and attach to
trim flange.
2. Tear out perforated area of gasket.
3. Install gasket support plate over receptacle
(B Series Flange only).
4. Place gasket over support plate.
5. Attach cover with four (4) flat head screws.
CAT. NO. 828R SHOWN
CAT. NO. 828GFITC SHOWN
Gasket
Support Plate
Gasket
Tear Out
Gasket
Support
Plate
NOTE: Refer to current version of Instruction Sheet 1 005 001
for installing adjustable partitions required for the
838TAL Series Covers.
NOTE: All Trim Flanges are supplied with adjusting screws
for a maximum upward adjustment of 1/2" [12.7mm].
Consult factory for upward adjustment greater than
1/2" [12.7mm].