Legrand SPDU8-1U User Manual User Manual
Page 9
6
Figure 12 - Implemented MIB Description, List of MIB object
DEFINITION
OID
RETURNED MESSAGE
systemModel
.1.1
System Model number. Read only.
systemName
.1.2
The system name or site name. Read only.
powerOutletNum
.1.3
Number of power outlets on the system. Read only.
serialPortNum
.1.4
Number of console ports on the system. Read only.
systemUpTime
.1.5
Seconds since the system in operation.
swVersion
.1.6
Firmware version
Outlet Sequence
outletIndex
.2.1
Index for the outlet table
outletName
.2.2
Outlet socket name. Read/Write.
outletStatus
.2.3
Outlet socket ON/OFF status. Read only.
outletAction
.3.4
Change outlet state to ON, OFF or Reboot.
Write only.
powerOutlet4OpStatus
.3.2.5.0
Read/Write. Applicable to NPC/NP systems.
Envro/Current Sequence
enviroIndex
.3.1
Index for the table
currentAlarmThreshold
.3.2
Aggregated AC current draw threshold for each power inlet (or power cord).
currentDrawStatus1
.3.3
First AC current monitoring reading. For a system equipped with single power
cord, this the valid current reading. For dual power corded system, this is the
first part of the AC current reading.
CurrentDrawStatus2
.3.4
For dual power corded system, this is the AC current reading for the second
power inlet (or power cord).
currentDrawMax1
.3.5
Maximum aggregated AC current draw value was captured for the first power
inlet (or power cord). For a system equipped with single power cord, this is
the valid current reading. For dual power corded system, this is the first part
of the AC current reading.
CurrentDrawMax2
.3.5
Maximum aggregated AC current draw value was captured for the 2nd power
inlet (or power cord).
temperatureThreshold
.3.6
Environment temperature threshold in F.
temperatureReading
.3.7
Temperature reading in F. Value is zero when the temperature probe is not
installed.
Event Notifications
opEvents
.100.1
Explicit operation events. Last TRAP/Notification sent. The messages include
outlet power status changes, AutoPing/Reboot events, system power on
event, user login/logout event,
CurrentThresholdCross-Event
.100.2
Current draw (Amps) crosses the defined threshold for inlet 1 or 2."
temperatureThresholdCrossEvent
.100.3
Environment temperature reading (in F) crosses predefined threshold.
E N T E R P R I S E O I D : 1 . 3 . 6 . 1 . 4 . 1 . 2 1 7 2 8 . 2 . 4 . 1
- SPDU16-2U User Manual SPDU20-0U User Manual WKD ProSeries Underfloor Duct Opening Reducer 880CM1-1 880CM2-1 880CM3-1 880CS1-1 880CS1-NA 880CS2-1 880CS2-NA 880CS3-1 880CS3-NA 880M1 880M2 880M3 880S1 880S2 880S3 828MAAP PCIQ PDU-TS1 Temperature Sensor WKD ProSeries Underfloor Duct Nonmetallic Fittings 525 Series Service Fittings RC7AP AMD8 Abandonment Plugs AV3ATCBK AV3ATCGY AV3ATCVY AV3ATCAL AV3ATCBS AV3ATCAA AV3ATCAB CCWB Series Wall Boxes 24DWND 24DWNR 881 Series Ratchet-Pro Multi-Service Round Floor Box