Complete Assembly:

Step 6. Cat. Nos. RC7ATC or RC7ATJTC

Step 7. Wire the power circuit.

Wire the Poke-Thru device.
(Can be completed above floor.)
Refer to wiring schematic in Step 8.

Step 8. Connect Poke-Thru conductors according

Step 9. If circuit is connected to an isolated ground,

to required device configuration. See

apply IG icon on receptacle slide as shown.

schematic below.

CAUTION: Receptacle mounting means not grounded. Grounding wire

NOTE: The orange triangle shall only be placed on devices

connection required. For isolated ground wiring; connect

that are wired for isolated ground. See NEC 250-146(d).

ground leads to a separate isolated grounding conductor.
See NEC 250-146(d).

2

Two #6-32 Slide Cover
Mounting Screws

Outlet Box

Cover Plate Screw

WHITE or NEUTRAL
from branch circuit

WHITE

from poke-thru receptacle

BLACK or HOT
from branch circuit

BLACK
from poke-thru receptacle

GREEN (jumper wire)

from poke- thru junction box

GREEN

from poke-thru receptacle

CONVENTIONAL WIRING SCHEMATIC

WHITE or NEUTRAL
from branch circuit

WHITE
from poke-thru receptacle

BLACK or HOT

from branch circuit

BLACK
from poke-thru receptacle

GREEN (jumper wire)
from poke-thru junction box

ISOLATED GROUND
from branch circuit

GREEN
from poke-thru receptacle

ISOLATED GROUND WIRING SCHEMATIC

GREEN or GROUND
from branch circuit
SYSTEM GROUND

GREEN or GROUND
from branch circuit
SYSTEM GROUND

WARNING:

Ground wire from junction box must be connected to SYSTEM GROUND.