Legrand RC7APTCGY User Manual
Rc7 poke-thru series, Installation instructions
IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: RC7STC, RC7ATC, RC7ATJTC, RC7CTC, RC7CTJTC, and RC7SHTC
RC7ATC-LJB, RC7ATJTC-LJB, RC7ATCLJB25 and RC7ATJTCLJB25
CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.
Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.
Step 1. Layout and locate position of hole(s).
Step 2. Remove 6 1/2" [165mm] section from carpet
or tile. Use template provided.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.
NOTE: Be certain to drill hole at least 4" [102mm] from any wall
NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.
or pillar to leave enough room for Poke-Thru cover assembly.
Step 3. Core drill hole.
Step 4. Stem Assembly:
Step 5. Cover Assembly:
Catalog No. RC7STC.
Catalog No. RC7CTC
Insert stem into hole.
or RC7CTJTC. Remove
disposable plate and replace
with carpet/tile flange. Install
with four #6-32 x 1/4"
[6.4mm] FHMS.
24" [610mm] Min
Center – Center
6 1/2"
[165mm] Diameter
CAUTION: Poke-Thru cannot be rotated
in hole after insertion into floor.
3" Diameter Core Drill
3 1/16" [78mm] Actual Diameter
Push Down
Four #6-32
x 1/4" FHMS
RC7 Poke-Thru Series
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 1 001 628 R2 – Updated April 2005
Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.
All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are
UL Listed to U.S. and Canadian safety standards, made for
interior use only, and should be installed in conformance with
current local and/or the National Electrical Code.