Step 9. Make electrical connections in junction box
Step 10. Wiring Diagram. Connect receptacle leads
according to wiring diagram.
to branch circuit conductors as required.
WARNING: Ground wire from junction box must be connected
to SYSTEM GROUND.
CAUTION:
Receptacle mounting means not grounded.
Grounding wire connection required. For isolated
ground wiring, connect ground leads to a separate
isolated grounding conductor See NEC250-146(d).
Step 11. If circuit is connected to an isolated ground, apply IG icon on receptacle slide as shown.
NOTE: The orange triangle shall only be placed on devices
that are wired for isolated ground. See NEC 250-146(d).
Circuit “B”
Circuit “A”
Circuit “A”
Circuit “B”
Line
Black
Red
Neutral
White
White w/Blue Stripe
Ground
Green
Green w/Yellow Stripe
Electrical Wiring Chart
NOTE: Factory supplied junction box shown. Junction boxes
must be located in an accessible location. Poke-Thru
devices with an “LJB” or “LJB25” suffix are supplied