Dampers Supported From Ductwork Above cont...

Recess Mounted Air Inlet Or Outlet Devices

Figure 4

t0QFOJOHJODFJMJOHNFNCSBOF TFFQBHF QBSBHSBQI

JTNPSFUIBOPOFJODIMBSHFSUIBOOPNJOBMTJ[FPG
ceiling damper (i.e. if the radiation damper is 12 in.
diameter [305mm] (nominal), the ceiling membrane
opening is larger than 13 in. diameter [330mm]).

t5IFSNBMCMBOLFUJTSFRVJSFE TFF1BHF QBSBHSBQI

t$POOFDUJPOPGDFJMJOHSBEJBUJPOEBNQFS BJSEFWJDF

neck, and steel duct drop (see page 2, paragraph 4)
may be satisfied as follows:

1.

Ceiling radiation damper may be connected
directly to the air device neck and then the duct
drop connected to the damper (see Detail B,
Figure 4).

.PEFMT$3%NBZCFJOTUBMMFEBTTIPXOJO'JHVSF

All hanger wires
must be vertical

(not splayed)!

Steel Duct

16 ga. x 1 1/2 in.
(1.5mm x 38mm) Steel
Channels (with 9/16 in.
(14mm)minimum flanges)

Steel Duct
Drop

Thermal
Blanket

Ceiling
Radiation
Damper

Air (Inlet or Outlet) Device

Detail B

9 3/4 in.

(248mm)

Maximum