beautypg.com

Installation, Installation guidelines – Greenheck Ceiling Radiation Dampers (826252) User Manual

Page 18

background image

1) CRD’s are shipped from the factory with the blades in

the closed position. The fusible link must be installed
at the time of installation such that the blades are held
open as shown in Figure 2.

2) Fasteners (screws, bolts, rivet, etc.) used for installation

must not interfere with blade operation.

3) Flexible duct must be Class I or 0 type, bearing the

UL listed mark. Steel duct must be a minimum 28 ga.
(.5mm) and maximum 20 ga. (1mm).

4) Ceiling damper must be installed as described in these

installations.

5) Ceiling penetration shall be located between floor/

ceiling trusses.

6) Dampers supplied without a factory supplied plenum

box require a steel or ductboard plenum to be field
installed (see pages 4 and 5).

7) Dampers shipped with factory attached plenums MUST

be installed prior to sheetrock ceiling installation.

Installation

1) The damper assembly is to be attached to the trusses

using 2 - 1 in. x 1 in. x 16 ga. (25mm x 25mm x 1.5mm)
or 2 - 1 1/4 in. x 1 in. x 20 ga. (32mm x 25mm x 1mm)
mounting angles. See Figure 3 for alternate mounting
angle detail. Attach each mounting angles to the
damper with a minimum of 2 - #8 screws or 5/32 in.
(4mm) diameter steel rivets.

Note: Make sure the fasteners do not interfere with the
damper operation.

2) Install the damper assembly, with attached mounting

angles, between the trusses as shown in Figures 4 - 7
and attach mounting angles to the trusses using 4 - 1¼
in. long steel screws per mounting angle.

3) For grille mount installations, the grille/diffuser frame

shall be steel. The grille/diffuser shall be attached with
a minimum of 4 - 1 in. (25mm) long #6 screws run
through the gypsum wall board into the plaster flange
(Figure 4 and 5).

4) For duct mount installations, 1 in. x 1 in. x 24 ga.

(25mm x 25mm x 0.7mm) retaining angles shall be
installed on all four sides and shall be attached with a
minimum 4 - 1 in. (25mm) long #6 screws run through
the gypsum wallboard into the plaster flange (Figure 6
and 7).

Installation Guidelines

Figure 2

1/2 in.
mini

mum

3 in.

3 in.

1 in.

Figure 3 - Alternate Mounting Angle

(provided by others)

1. Damper
2. Mounting Angle
3. Plaster Flange
4. Gypsum Board
5. Grille
6. RC Channel
7. Steel Plenum

Figure 4: Grille Mount with Steel Plenum

Note: For grille mount installations, the damper blades shall be
maximum 3 1/4 in. (83mm) above the top of the ceiling plane. For
duct mount installations, the damper blades shall be maximum 1/8 in.
(6mm) above the top of the ceiling plane.