Strainer Cleaning
Clean the strainer immediately after the pump has been installed and tested, and again after a
few hundred gallons have been delivered. Thereafter, once every six months, or as required.
The procedure for cleaning the strainer can be found in the Maintenance and Troubleshooting
section.
Belt
Since belts do stretch slightly during the first few minutes of operation, check the belt tension
after completing the operational test. See the Maintenance and Troubleshooting section for
details.
Reconfiguration of Pump Pulley for Hand Crank Operation
4
3
2
1
Before a hand crank can be used to pump fuel, you must reconfigure the pump pulley as
follows:
1
Unscrew and remove the screw (4), lock washer (3), washer (2), and pump pulley (1).
2
Flip the pump pulley (1) around so the shorter groove at the back is exposed at the front end.
3
Replace the pump pulley (1), washer (2), lock washer (3), and screw (4) and tighten the screw.
4
Engage the hand crank belt to the shorter groove.