Islander to FleetKey Conversion

04/15/03

9

CONFIGURING THE SITE CONTROLLER


A Key option is available for Islander II sites. The following configuration adjustments must be
made to the Site Controller configuration for this option.

SYSTEM PARAMETERS (SYS PAR)


The following setting must be used to configure the Site Controller to accept keys.

Page 2: Club card format - field widths

Digits in limitation code = 1
Digits in authorization code = 1
Digits in price level = 1
Digits in restriction code = 1
Digits in expiration date = 4

Page 3: Club card format - offsets

Limitation code offset = 0
Authorization code offset = 1
Price level offset = 2
Restriction code offset = 3

Reader verification - page 4

The key option on the CFN allows the PIN number to be stored on the key. If you are using

this option, when the user enters the PIN at the reader, it is verified against the PIN stored on
the key. These PIN numbers do not use the standard CFN algorithm and are verified at the
reader. In order to use this option, you must set the following reader verification parameters:

Require PIN (reader) = none
Check PIN (reader) = none

NOTE:

The check digit on the key must be set to require PIN in order to verify the key
PIN number. Refer to the KE200 Key Encoder/Maintenance Terminal Operation
Manual, C08380 for more information.

If you are using key and card combinations (verifying the PIN for the card), code keys (using
the Lookup tables), or verifying the PIN based on an Account field number and not the
number stored on the key, you must set the following reader verification parameters:

Check PIN (reader) = club

NOTE:

The check digit on the key must be set to NOT require PIN. Refer to the KE200
Key Encoder/Maintenance Terminal Operation Manual, C08380 for more
information. If you are verifying the PIN based on an Account field number from
the key, set the following parameter:

Require PIN (reader) = club