Installing atlas npt discharge kit (m06648k001) – Gasboy NPT Disch Kit User Manual
Page 7

MDE- 4533 Instructions for Installing Atlas NPT Discharge Kit (M06648K001) • December 2005
Page 7
Installing Atlas NPT Discharge Kit (M06648K001)
Installing Atlas NPT Discharge Kit (M06648K001)
To install the Atlas Discharge Kit, proceed as follows:
1
Remove the existing discharge fitting from the exterior of the unit, copper discharge tube and
meter discharge fitting.
Figure 2: Discharge Kit Assembly
O-ring
Serrated Hex nut
Mounting
bracket
90 Degree
painted elbow
Discharge
pipe grommet
U-bolt
Discharge
meter hose
fitting
Blanking
plate
Sheathing
1-inch Std.
pipe
2
Apply pipe sealant to the threads of the 1-inch pipe nipple (R11495-123).
Note: Use sealant approved for use with petroleum products.
3
Insert the nipple into the discharge fitting (M04624B020) and tighten it.
Note: Ensure that you do not overtighten the nipple.
4
Apply oil to the O-ring (N16891-32) and insert it into the O-ring groove in the meter
discharge.
Note: Ensure that the O-ring is properly aligned with the grooves while inserting.