2 remounting – Flowserve MX-85 Actuator User Manual
Page 73

Flow Control
Limitorque Actuation Systems
FCD LMAIM1341-00
MX-85/140 Maintenance and Spare Parts
65
5.5.2 Remounting
STEP 7
c
WARNING: Hazardous Voltage! Turn off all 
power sources to actuator before remounting 
terminal block assembly. Power sources may 
include main power or control power.
If necessary, to allow terminal block wiring bundle 
to pass across the end of the contactor and into the 
controls compartment, use a M3 hex key to loosen 
the two 4 mm contactor screws (#8-28). Pull con-
tactor assembly off the screws and lower assembly 
to create extra space for the wire harness to pass 
over the contactor and into the controls 
compartment.
7
8-28
STEP 8
Plug power leads L1, L2, and L3 from contactor 
assembly into terminal connectors L1, L2, and L3 
on back of terminal block. Verify that O-ring (#1-
20) is installed on back of terminal block. Lightly 
lubricate O-ring before installing terminal block.
8
1-20
Power
leads
STEP 9
Insert terminal block into terminal block mounting 
cavity.
9