beautypg.com

2 module led, 3 sp led, 2 module led -2 – Delta Electronics DeviceNet CME-DN01 User Manual

Page 20: 3 sp led -2

background image

Chapter 5 Troubleshooting| CME-DN01

5-2

Revision October 2007, 2006PDD23000003

State

Indication

Corrective Actions

Red LED

Network failure. Failed
duplicate ID or Bus-off.

1.

Ensure that all nodes have unique address.

2.

If all node addresses are unique, check

network for correct media installation.

3.

Ensure that the address is NOT in the illegal

range.

5.2 Module LED

State

Indication

Corrective Actions

LED is off

No power/not online

Ensure that the connected AC drive is powered
and connected to the CME-DN01.

Flashing

Green LED

Waiting for I/O data. No
I/O, or PLC is in program
mode

CME-DN01 has passed all operation tests and
waits to transmit I/O data between the CME-DN01
and the AC drives.

Green LED

I/O is in running mode

Flashing Red

LED

Configuration problem. Bad
CRC of CME-DN01
parameters or flash
program.

Reset internal I/O data of the CME-DN01. Please
refer to Data Configuration address assignment
for detail.

Red LED

Hardware Failure. Failed
internal or external RAM
test.

Return to the factory.

5.3 SP LED

State

Indication

Corrective Actions

LED is off

No power

No power is applied to the device.

Flashing

Green LED

CME-DN01 is reading the
factory settings of the AC
drives. CME-DN01 gets
parameters information of
the AC drives and
initializes some Identity
attributes.

Green LED

CME-DN01 and the AC
drives are communicating.

Flashing Red

LED

CRC check error/AC drives
return error information.

To check if the setting of communication format of
the AC drives is correct. Please refer to the