Chapter 3 Quick Start

3.1 Setting Steps for Installation

Step 1. Setting communication format of the AC drives to 19200 RTU 8, N, 2.

Step 2. Setting frequency source of the AC drives to operate from RS-485.

Step 3. Setting operation source of the AC drives to operate from communication interface.

Note: Refer to the following table for setting step 1, step 2 and step 3.

VFD-E

Description

P02-00=3

Master frequency determined by RS-485

P02-01=3

Operating instructions determined by the RS-485

communication

P09-01=2 19200

bits/second

P09-04=3

Modbus RTU mode, 8 bits, no parity and 2 stop bits

Step 4. Using RJ11 (6 pins) to connect RS-485 of the CME-DN01 and the AC drive.

Step 5. Adding the EDS files (generated from the auto EDS generator software, can be

downloaded from Delta website http://www.delta.com.tw/industrialautomation/) into DeviceNet

management software.

Step 6. Using the operation method of DeviceNet management software for CME-DN01

connection.

Note: Please make sure that VFD-E has set as above table. Or CME-DN01 cannot work

correctly. SP LED should be Green after finishing Step 4 and indicates the CME-DN01 is

communicating with the AC motor drive. If the SP LED is not ON, please refer to chapter 4

Troubleshooting to solve the problem.