Pr. Explanation

Settings

Factory

Setting

NOTE

4-08

Multi-Function Input Terminal 5(M5)

d18: Pause PLC Program
d19: Counter Trigger Signal
d20: Counter Reset
d21: Select ACI / Deselect AVI
d22: PID Function Disabled
d23: JOG FWD
d24: JOG REV
d25: The source of master

frequency is AVI.

d26: The source of master

frequency is ACI.

d27: Press UP/DOWN key to switch

forward/reverse (N.O.) motion

d28: Press UP/DOWN key to switch

forward/reverse (N.C.) motion

d29: M0: 0: RUN 1: STOP, M1: no

function, Direction is controlled
by keypad

d9

4-09

Line Start Lockout

d0: Disable
d1: Enable

d0

4-10 Up/Down

Mode

d0: Based on accel/decel time
d1: Up frequency according to

constant speed, down frequency
according to deceleration time

d2: Up frequency according to

acceleration time, down
frequenc according to constant
speed

d3: Constant speed

d3

4-11

Accel/Decel Rate of Change of
UP/DOWN Operation with Constant
Speed

0~1000, unit: 5 Hz/sec

d1


Group 5 Multi-Step Speed and PLC Parameters

Pr. Explanation

Settings

Factory

Setting

NOTE

5-00

1st Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-01

2nd Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-02

3rd Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-03

4th Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-04

5th Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-05

6th Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-06

7th Step Speed Freq.

d0.0 to d400 Hz

d0.0

5-07 PLC

Mode

d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program

cycles

d3: Execute one program cycle step

by step

d4: Continuously execute one

program cycle step by step

d0