Temperature Sensor Mounting For
GalaxyPro Revolution Displays

page 4 of 4

terminate the temperature sensor from one display to the other.

Interconnect Locations – M4 Controller
Primary
(A31-TB1)

Field
Cabling

Secondary
(A31-TB1)

Pin 2 (GND CAN)

Black

Pin 2 (GND CAN)

Pin 3 (CAN H)

Green

Pin 3 (CAN H)

Pin 4 (CAN L)

White

Pin 4 (CAN L)

One end terminates at the 4-position terminal
block (TB1) on the primary display. The other
end terminates at the 4-position terminal block
(TB1) in the second display. Refer to Figure 6

and the following table for correct
interconnect locations.

Note: Do not connect the wire to pin one on either display.

1.6 Sensor Replacement

If the temperature sensor board or wiring
malfunctions, access it by:

Figure 7: Temperature Sensor Diagram

1. Open the temperature sensor housing by

removing the four nuts from the bottom and
then removing the five bottom disks. Refer to
Figure 7 for details on sensor housing
disassembly.

2. Label the wires connected to the temperature

sensor board and then disconnect the cable
from the sensor terminal block in the
temperature sensor housing.

3. Remove the two screws holding the board to

the plastic disk. Install the new board and
replace the two screws.

4. Reconnect the cable to the temperature sensor board, making sure all the wires make a

good electrical connection.

Figure 8: Temperature Sensor Wiring

5. Route wires around the sensor board as shown

in Figure 8 and reassemble the sensor enclosure.

DD1514799 Rev 0

29 January 2009