2.7 Power Requirements

Item

Limits

Input power

24 VAC/VDC ± 10%, 47–63 Hz, 6 VA

2.8 General Specifications

Item

Description

Protection

All inputs and outputs (except for relay outputs and communications ports)

are over-voltage protected up to 24 VAC and short-circuit protected.

Environmental

Operating temperature 0° to +60°C. Storage temperature –40°C to +85°C.

Relative humidity 10–95%, non-condensing.

Weight

0.6 lbs. (0.27 kg).

2.9 LED Indicators

LED Indicator

Indication

UI1–UI8 Configured as Analog Input

Green: > 1% of range, otherwise off

UI1–UI8 Configured as Temperature Input Green: sensor detected

UI1–UI8 Configured as Contact Input

Green: contact closed, otherwise off

UI1–UI8 Configured as Pulse Input

Green: pulse sensed, otherwise off

BI1–BI4 Contact Closure

Green: contact closed, otherwise off

AO1–AO4 Analog Output

Green: commanded output

BO1-BO4 Binary Output

Green: commanded output

Ethernet

Green: Link established; flashes with activity

2.10 Electromagnetic Compatibility

Standard

Test Method

Description

Test Levels

EN 55024

EN 61000-4-2

Electrostatic Discharge

6 kV contact

EN 55024

EN 61000-4-3

Radiated Immunity

10 V/m, 80 MHz to 1 GHz

EN 55024

EN 61000-4-4

Fast Transient Burst

1 kV clamp & 2 kV direct

EN 55024

EN 61000-4-5

Voltage Surge

1 kV L-L & 2 kV L-Earth

EN 55024

EN 61000-4-6

Conducted Immunity

10 V (rms)

EN 55024

EN 61000-4-11 Voltage Dips & Interruptions

1 Line cycle, 1–5 s @100% dip

EN 55022

CISPR 22

Radiated Emissions

Class A

EN 55022

CISPR 22

Conducted Emissions

Class B

CFR 47, Part 15 ANSI C63.4

Radiated Emissions

Class A