5.2.2

Universal Input

— Configured as Binary Input

(Channels UI1–UI8)

You can accept a binary input with any channel UI1–UI8 as follows:

On the Main Page (

Figure 13

), click a title link from among UI1–UI8.

Under BAS Channel Configuration in the new page that appears (

Figure 20

),

set the Channel Type to Binary Input.

In the BACnet Object Configuration (lower) section of the screen, all items

are as described in Section

5.2

above

— but Units defaults to NO_UNITS.

Attach your device to the pair of BASC20 pins for the chosen channel

— so

that the more positive connection is to pin A and the more negative to pin C.

Figure 20