5.2.6

Analog Outputs

(Channels AO1–AO4)

Voltage in the range of 0

–10 VDC (with up to 4 mA of current) can be outputted by

assigning analog outputs. Configure an output using a web browser. For DC
voltage, the output voltage is applied to point A with respect to C (common).

Any channel AO1–AO4 can be used to provide an analog voltage output. The
BACnet type will be Analog Output. To configure an analog output:

On the Main Page (

Figure 13

), click a title link from among AO1–AO4.

Under BAS Channel Configuration (lower) section of the new screen that

appears (

Figure 24

), the Channel Type will be Analog Output (read-only).

In the BACnet Object Configuration (lower) section of the screen, all items

are as described in Section

5.2

above

— but Units defaults to VOLTS.

Attach your device to the pair of BASC20 pins for the chosen channel

— so

that the more positive connection is to pin A and the more negative to pin C.

Figure 24

— Analog Output Configuration