B.2.1 start character, B.2.2 device address – Comtech EF Data RC-1160 User Manual
Page 58

Remote Control
Revision 1
RC-1160 RC-1260 Redundancy Switch Controllers
MN-RC1160RC1260
B-2
The general message structure is as follows:
•
Start Character
•
Device Address
•
Command/Response
•
End of Message Character
B.2.1 Start Character
A single character precedes all messages transmitted on the communications link. This character flags the start
of a message. This character is:
•
“<” for commands
•
“>” for responses
B.2.2 Device Address
The device address is the address of the RC-1160/-1260 which is designated to receive a transmitted command,
or which is responding to a command.
Valid device addresses are 1 to 3 characters long, and in the range of 1 to 255. Address 0 is reserved as a global
address which simultaneously addresses all devices on a given communications link. Devices do not
acknowledge global commands.
Each RC-1160/-1260 which is connected to a common remote communications link must be assigned its own
unique address. Addresses are software selectable at the RC-1160/1260, and must be in the range of 1 to 255.