Installation

(for qualified installers only)

37

Travis Industries

4140312

100-01305

Mantel Requirements

 Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured

from the face of the fireplace) must fall in the shaded portion of the table.


 Any material that protrudes more than 3/4” from the non-combustible facing is considered a mantel

and must meet the mantel requirements.

a

b

If you have a tapered mantel, measure the

mantel height at the point where it

protrudes 3/4” in front of the face.

Maximum Mantel Depth (b)

Mantel

Height

Above

Face (a)

0”

1”

2”

8”

7”

6”

5”

4”

3”

9”

0” 1” 2” 3” 4” 5” 6” 7” 8” 9” 10” 11” 12”

See “Face Dimensions”

Combustible mantel columns (legs) that

protrude more than 3/4” from the glass

frame must meet the sidewall clearance (1”

from the face). If they protrude 3/4” or less,

they do not have a minimum clearance.

Non-combustible mantel columns do not

have a minimum clearance.

Mantel

(combustible or non-combustible)