100-01305

Electrical Connection (required)

 The electrical line to the grounded receptacle inside the fireplace must be installed by a qualified

installer and must meet all local codes.

 Make sure the household breaker is shut off prior to working on any electrical lines.
 The appliance, when installed, must be electrically grounded in accordance with local codes or, in the

absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical
Code, CSA C22.1.

 The electrical line must be a min. 14 gauge, and supply 120 Volts at 60 Hz (2 Amps).

Caution:

Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation.

d

Remove the cover from the

fireplace junction box.

The connection wires and a romex clamp

are inside the junction box.

Remove the knock-out from the cover plate.

NOTE: An alternative knock-out is

provided in the base of the

fireplace if you wish to run the

electrical line from below.

Secure the romex connector to the cover plate. Route

the electrical line through the cover plate and attach the

electrical leads. Replace the cover plate.

a

b

c