Fireplace Placement Requirements

 The fireplace requires a 1/2" clearance from the angled sides and back of the fireplace to the framing

members. No material (insulation, framing, etc.) may be placed into this area.

 Fireplace must be installed on a level surface capable of supporting the fireplace and vent.
 Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet).
 This heater may be placed in a bedroom.

Clearances

 When installed, walls in front of the fireplace must be a minimum 1" to the side of the fireplace.
 Due to the high temperature, the heater should be located out of traffic and away from furniture and

draperies.

 Fireplace must be placed so the vents below and above the glass do not become blocked.

Raised Fireplaces

 The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace

(95 Lbs.) and vent.

Raised

Platform

Optional Hearth

Minimum

57"

Ceiling

Min. Enclosure Height
Top Vent = 48"
Rear Vent = 34-1/4"