28 installation, For qualified installers only) – Avalon Firestyles Bed & Breakfast Installation User Manual
Page 28
28 Installation
(for qualified installers only)
Travis Industries
4140312
100-01305
Rear Vent Configuration with Horizontal Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
Only one horizontal elbow may be used.
Use 8" diameter vent.
5 feet
10 feet
0 feet
0 feet
5 feet
5 feet
0 feet
0 feet
10 feet
5 feet
10 feet
14'
(max)
10 feet
14 feet
(max)
NOTE:
Horizontal sections require a 1/4" rise
every 12" of travel.
14 feet
(max)
14 feet
(max)
NOTE:
Restrictor positions are based upon lab tests.
The ideal restrictor position may vary slightly.
Restrictor Position # 1 (stock)
Diffuser Position # 1 (stock)
Restrictor Position # 1 (stock)
Diffuser Position # 2
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a
vertical elbow
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
H2