28 Installation

(for qualified installers only)

Travis Industries

4140312

100-01305

Rear Vent Configuration with Horizontal Termination

 The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and

diffuser positions.

 Up to four elbows (45° or 90°) may be used.
 Only one horizontal elbow may be used.
 Use 8" diameter vent.

5 feet

10 feet

0 feet

0 feet

5 feet

5 feet

0 feet

0 feet

10 feet

5 feet

10 feet

14'

(max)

10 feet

14 feet

(max)

NOTE:

Horizontal sections require a 1/4" rise

every 12" of travel.

14 feet

(max)

14 feet
(max)

NOTE:

Restrictor positions are based upon lab tests.

The ideal restrictor position may vary slightly.

Restrictor Position # 1 (stock)

Diffuser Position # 1 (stock)

Restrictor Position # 1 (stock)

Diffuser Position # 2

This is considered a horizontal

elbow (it does not matter

whether it turns right or left).

It may be a 90° or 45° elbow.

This is considered a

vertical elbow

Horizontal length is calculated by adding

both lengths of horizontal run

(Horizontal Length = H1 + H2).

H1

H2