Table 2, Maximum ac current ratings, pfc models -9, Maximum ac current ratings, non-pfc models -9 – AMETEK SGI Series User Manual
Page 31: Input/output connectors -9, O table 2, N table 2

Sorensen SGI Series
Installation
M550221-01 Rev AA
2-9
Model Ratings
Input Line Current, A (RMS)*
Voltage
Model
AC Input
Option
Code
Input
Voltage,
VAC
5 kW 10 kW 15 kW 20 kW 25 kW 30 kW
40V-1000V
C
208/230
20
39
59
79
98
118
D
380/400
11
22
32
43
54
65
E
440/480
9
19
28
37
47
56
4 kW 8 kW 12 kW 5 kW 10 kW 15 kW
10V-15V
C
208/230
16
32
47
N/A
N/A
N/A
D
380/400
9
17
26
N/A
N/A
N/A
E
440/480
7
15
22
N/A
N/A
N/A
20V-30V
C
208/230
N/A
N/A
N/A
20
39
59
D
380/400
N/A
N/A
N/A
11
22
32
E
440/480
N/A
N/A
N/A
9
19
28
* AC input current could vary as a result of actual power factor; refer to specifications section for
power factor dependency
Table 2
–1. Maximum AC Current Ratings, PFC Models
Model Ratings
Input Line Current, A(RMS)*
Voltage
Model
AC Input
Option
Code
Input
Voltage,
VAC
5 kW 10 kW 15 kW 20 kW 25 kW 30 kW
40V-800V
C
208/230
24
47
71
95
118
142
D
380/400
13
27
40
54
67
81
E
440/480
12
24
36
49
61
73
* AC input current varies depending on actual power factor; refer to specifications section on power
factor
Table 2
–2. Maximum AC Current Ratings, Non-PFC Models
Connector
Function
Connection
L1
– AC, L2 – AC, L3 – AC,
Chassis - GND
AC input power; see Table 2
AC mains 3-phase
input
Pos. Bus Bar,
Neg. Bus Bar
DC output power; see Table 2
User load
Analog Interface
Connector (J1)
Control interface; see Table 3
User controller
Remote Sense Connector
Remote voltage sensing; see Section 3.14
Output load
Parallel In/Out
Parallel operation; see Section 3.16
Master/Slave units
Table 2
–3. Input/Output Connectors