1.2.3 SGI Series Voltage and Current Specifications

The following tables present the specifications for rated voltage and current, and ripple/noise for

the 10V-1000V models.

Rated

Voltage,

VDC

Rated Current, ADC

Ripple/

Noise**

RMS,

mV

Ripple/

Noise*

PK

–PK,

mV

4 kW

5 kW

8 kW

10 kW

12 kW

15 kW

0-10

††

0-400

N/A

0-800

N/A

0-1200

N/A

20

50

0-15

††

0-267

N/A

0-534

N/A

0-801

N/A

20

50

0-20

††

N/A

0-250

N/A

0-500

N/A

0-750

20

60

0-30

††

N/A

0-167

N/A

0-334

N/A

0-501

20

60

Rated

Voltage,

VDC

Rated Current, ADC

Ripple/

Noise**

RMS,

mV

Ripple/

Noise*

PK

–PK,

mV

5 kW

10 kW

15 kW

20 kW

25 kW

30 kW

0-40

0-125

0-250

0-375

0-500

0-625

0-750

20

75

0-50

0-100

0-200

0-300

0-400

0-500

0-600

20

75

0-60

0-83

0-167

0-250

0-333

0-417

0-500

20

75

0-80

0-63

0-125

0-188

0-250

0-313

0-375

20

100

0-100

0-50

0-100

0-150

0-200

0-250

0-300

20

100

0-160

0-31

0-63

0-94

0-125

0-156

0-188

25

150

0-200

0-25

0-50

0-75

0-100

0-125

0-150

25

175

0-250

0-20

0-40

0-60

0-80

0-100

0-120

30

200

0-300

0-17

0-33

0-50

0-67

0-83

0-100

30

200

0-330

0-15

0-30

0-45

0-61

0-76

0-91

30

200

0-400

0-12

0-25

0-38

0-50

0-63A

0-75

30

300

0-500

0-10

0-20

0-30

0-40

0-50

0-60

50

350

0-600

0-8

0-17

0-25

0-33

0-42

0-50

60

350

0-800

0-6.2

0-12.5

0-18.7

0-25

0-31.2

0-37.5

80

500

0-1000

0-5

0-10

0-15

0-20

0-25

0-30

100

650

* PK-PK ripple/noise, over 20 Hz to 20 MHz bandwidth, is measured across a 1 µF capacitor at

the end of a 6’ load cable with the supply operating at full load and nominal AC line voltage.

** RMS ripple/noise, over 20 Hz to 300 kHz bandwidth, is measured directly across the output

terminals with the supply operating at full load and nominal AC input line voltage.

Power level not available in 6U models, but could be produced with paralleled 3U units;

up to

75 kW could be produced by paralleling up to five units. Paralleling will increase ripple/noise.

††

Models from 10V-30V are not available in 6U chassis.