Sorensen SGI Series

Installation

M550221-01 Rev AA

2-5



WARNING!
A minimum two-person lift is required for the 3U SGA Series power
supply, which weighs up to 110 lb (50 kg) depending on the model.

Refer to Figure 2-1 for 3U rack mount assembly drawing for the following
instructions:

1. Install the slide sections, 1C , on both sides of the power supply chassis with

screws (three on left side and four on right side). Ensure that the latch spring
orientation is as shown in Note 1 .

2. Install the brackets, 2A and 2B , to the stationary slide sections, 1A , with the

hardware provided by the slide supplier as shown in Note 3 .

3. Ensure that stopper orientation of slide sections, 1B , is as shown in Note 2 .

Adjust the location of the mounting brackets as required for the particular type
of cabinet vertical rails utilized.

4. Mount the stationary slide sections, 1A , (with brackets already installed) into

the cabinet using appropriate hardware (e.g. bar nuts, cage nuts, clip nuts),
while ensuring that they are level front to back and left to right of the cabinet
rails.

5. Insert power supply chassis with slide sections, 1C , into slide sections, 1B .

6. Secure the front panel of the power supply chassis to the cabinet rack rails

using the screws provided in the ship kit.