6 example of calculation, 7 standard values for a range of cable types, 6wiring – Pilz PDP67 F 4 code User Manual
Page 25: 3 preparing for operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-9
6.3
Preparing for operation
6
Wiring
6.3.1.6
Example of calculation
Example of calculation
6-
Verdrahtung_PDP_PSEN_Leitungslänge-Spannungsabfall-Beispiel
A 0.25 mm² sensor cable is used.
Voltage drop per 10 m and per 100 mA: 0.15 V
6.3.1.7
Standard values for a range of cable types
Standard values for a range of cable types
6-
Verdrahtung_PNOZ ml2p_Leitungslänge-Spannungsabfall-Richtwerte
Guidelines for calculating the voltage drop on various cable types
Cable type
Voltage drop per 10 m and per 100
mA
PSS SB BUSCABLE LC
0.1 V
Sensor cable 0.25 mm
2
0.15 V
Sensor cable 0.34 mm
2
0.11 V
Sensor cable 0.5 mm
2
0.07 V
PNOZmulti Base Unit
4*I0+I1+I2+I3+I4
865 mA
U = 1,3 V
I0+I4 =
205 mA
U = 0,923 V
2*I0+I3+I4
410 mA
U = 0,3 V
3*I0+I2+I3+I4
615 mA
U = 0,92 V
10 m
5 m
10 m
30 m
I4
»
200 mA
I3
»
200 mA
I2
»
200 mA
I1
»
250 mA
PSEN
PSEN PSEN
PSEN
PSEN PSEN
PSEN
PSEN PSEN
PSEN
PSEN PSEN
PSEN
PDP67 F 4 code
I0=5 mA
PDP67 F 4 code
I0=5 mA
PDP67 F 4 code
I0=5 mA
PDP67 F 4 code
I0=5 mA